Safety Shut-off Valve (SSV), Direct-acting or Pilot-operated, According to DIN EN 14382
| Application | Device for transmission stations in gas networks for power plants and industrial facilities |
|---|---|
| Very low pressure loss due to axial flow | |
| Four release options, standard design with manual release | |
| High response accuracy | |
| Available with actuator systems: K 10a, K 11a/1, K 11a/2, K 16, K 17, K 18, K 19 |
|
| Function Class A (B) | |
| Easy maintenance | |
| Optionally with vent valve RMG 915 | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE registration according to PED | |
| Max. admissible pressure PS | = 100 bar |
| Max. operating pressure pmax | up to 100 bar |
| Outlet pressure range | For over-pressure Wdso 80 mbar to 90 bar For under-pressure Wdsu 10 mbar to 90 bar |
| Connection | DIN flange PN 25, PN 40 and Flange Class 300, Class 600 according to ANSI 16.5 in DN 200, DN 250, DN 300 |
| Response time t | → 0.1 s to 0.5 s |
| Additional features (as requested by customer) | Electromagnetic release Electric signal sensor for valve position “CLOSED” (proximity switch) |