Safety Shut-off Valve (SSV), Direct-acting or Pilot-operated, According to EN 14382
| Application | Device for industrial facilities and individual consumers |
|---|---|
| Also suitable for low-load lines in larger gas pressure regulating stations | |
| Compact and simple construction | |
| Easy to maintain due to exchangeable function units (cartridge assembly) | |
| Design with actuator systems: K 1a, K 2a/1, K 2a/2, K 16, K 17, K 18, K 19 | |
| Function Class A (B) | |
| Optionally with vent valve RMG 915 | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE-registration according to PED | |
| Max. admissible pressure PS | = 100 bar |
| Max. operating pressure pmax | up to 100 bar |
| Outlet pressure range | For over-pressure Wdso 50 mbar to 90 bar |
| For under-pressure Wdsu 10 mbar to 90 bar |
|
| Connection | - Pipe connections according to DIN EN ISO 8434-1 (DIN 2353), PN 100, for pipe diameters 10 mm thru 42 mm - DIN flange PN 25, PN 40 and Flange Class 300, Class 600 according to ANSI 16.5 with transition pieces in DN 25, DN 40 and DN 50 |
| Response time t | 0.1 to 0.3 s |
| Additional features | Electromagnetic release |
| (as requested by customer) | Electric signal sensor for valve position “CLOSED” (proximity switch) |
| Manual release | |
| Valve combination available together with RMG 200 and RMG 201 | |