RMG 675 Actuator, K 15a According to DIN EN 14382
| Application | Actuator systems for pilot-operated Safety Shut-off Valves. According to DIN EN 14382, actuator systems are integral part of SSVs |
|---|---|
| High response accuracy; low re-engagement differentials | |
| Easy operation and maintenance | |
| Function Class A (B) | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE registration according to PED in combination with RMG Gas Pressure Regulators According to DIN EN 14382, the pilot is an integral component of this device. |
|
| Max. admissible pressure PS | = 16 bar |
| Max. operating pressure pmax | up to 16 bar |
| Setting range | Over-pressure Wdso 30 mbar up to 1 bar |
| Valve seat diameter | 3 mm |
| Connection | Pipe connections according to DIN EN ISO 8434-1 (DIN 2353), for pipe diameters 12 mm |