Pipe size Inlet (DN) |
Pipe size Outlet (DN) |
Valve seat diameter in mm |
Flow rate coefficient KG* in m³/(h · bar) |
|---|---|---|---|
|
25 |
25 100 150 |
25 |
550 490 490 |
|
50 |
50 150 200 |
50 |
2,200 1,920 1,980 |
|
80 |
80 250 |
80 |
5,610 5,060 |
|
100 |
100 300 |
100 |
8,800 7,810 |
|
150 |
150 300 400 |
150 |
19,800 14,630 16,830 |
|
200 |
200 400 500 |
200 |
37,400 25,850 30,800 |
|
250 |
250 400 500 |
200 |
41,800 25,850 30,800 |
|
250 |
250 500 600 |
250 |
55,000 39,600 46,750 |
|
Setpoint spring |
Specific outlet pressure range Wds in bar |
|||
|---|---|---|---|---|
|
Spring |
Wire Ø |
Colour coding |
||
|
Control stage |
0 1 2 3 4 5 |
4.5 3.6 4.5 5 6.3 7 |
black blue black grey brown red |
0.3 to 1** 0.5 to 2 1 to 5 2 to 10 5 to 20 10 to 40 |
|
Control stage with metal-harmonica |
6 7 |
8/7 9 |
green white |
10 to 50 20 to 90 |
|
Automatic load limiting stage |
5 |
green |
0.5 to 15 automatic: above pd |
|
|
Outlet pressure range (pdrange) in bar |
Accuracy Class AC |
Lock-up pressure Class SG |
|---|---|---|
|
0.3 to 0.5 > 0.5 to 1 > 1 to 2.5 > 2.5 to 5 > 5 |
10 10 2.5 1 1 |
30 20 10 10 5 |
|
Pipe size DN |
Revised design version |
Flange PN 25 + PN 40 |
Flange according to ANSI 16.5 |
|||
|---|---|---|---|---|---|---|
|
Inlet |
Outlet |
Class 300 RF |
Class 300 RTJ |
Class 600 RF/RTJ |
||
|
25 |
25 *100 *150 |
b b b |
200 360 360 |
197 359 359 |
210 365 365 |
210 365 365 |
|
50 |
50 *150 *200 |
b b b |
270 422 422 |
267 421 421 |
283 429 429 |
286 430 430 |
|
80 |
80 *250 |
b b |
310 512 |
318 516 |
333 523 |
337 525 |
|
100 |
100 *300 |
b b |
370 548 |
368 548 |
384 555 |
394 560 |
|
150 |
150 *300 *400 |
c c c |
508 550 550 |
508 550 550 |
508 550 550 |
508 550 550 |
|
200 |
200 *400 *500 |
c c c |
610 650 650 |
610 650 650 |
610 650 650 |
610 650 650 |
|
**250 |
*250 *400 *500 |
c c c |
630 660 660 |
630 660 660 |
630 660 660 |
630 660 660 |
|
250 |
250 *500 *600 |
c c c |
752 752 752 |
752 752 752 |
752 752 752 |
752 752 752 |