RMG 505 Gas Pressure Regulator

Valve specifications

Pipe sizes

DN

Valve seat diameter

in mm

Flow rate coefficient

KG* in m³/(h · bar)

Face-to-face dimension in mm

50/100

80/150

100/200

50

80

100

1,700

4,600

7,000

380

550

550

*) Flow rate coefficient for natural gas: ρb = 0.83 kg/m³, t =15 °C

Specific outlet pressure range with pilot RMG 630/630-1 (formerly RMG 640)

Setpoint spring

Specific outlet
pressure range

Wds in bar

Spring
no.

Wire Ø
in mm

Colour coding

Control stage

0

1

2

3

4

5

4.5

3.6

4.5

5

6.3

7

black

blue

black

grey

brown

red

0.3 to 1**

0.5 to 2

1 to 5

2 to 10

5 to 20

10 to 40

Control stage with metal-harmonica

6

7

8/7

9

green

white

10 to 50

20 to 90

Automatic load limiting stage

5

green

0.5 to 15

automatic: above pd

Accuracy Class and lock -up pressure Class with pilot RMG 630

Outlet pressure range

(pd range) in bar

Accuracy Class

AC

Lock-up pressure Class

SG

0.3 to 0.5

> 0.5 to 1

> 1 to 5

> 5

20

10

2.5

1

30

20

10

5

Accuracy Class and lock -up pressure Class with pilot RMG 630-1 (formerly RMG 640)

Outlet pressure range

(pdrange) in bar

Accuracy Class

AC

Lock-up pressure Class

SG

0.3 to 1

> 1 to 3

> 3 to 5

> 5 to 10

> 10 to 40

> 40

20*/30

20

10

5

2.5

1

30*/50

30

20

10

10

5

*) Better accuracy and lock-up pressure classes apply if inlet pressure variation < 8 bar.
**) Type with larger measuring diaphragm.

Specific outlet pressure range with pilot RMG 650

Setpoint spring

Specific outlet pressure range Wds in bar

Spring
no.

Wire Ø
in mm

Colour coding

Control stage

0

1

2

3

4

5

4.5

3.6

4.5

5

6.3

7

black

blue

black

grey

brown

red

0.3 to 1*

0.5 to 2

1 to 5

2 to 10

5 to 20

10 to 40

Control stage with metal-harmonica

6

7

8/7

9

green

white

10 to 50

20 to 90

Automatic load-limiting stage

5

green

0.5 to 15

automatic: above pd

*) Type with larger measuring diaphragm

Accuracy Class and lock -up pressure Class with pilot RMG 650 (single /double stage ) for monitor device

Outlet pressure range

(pd range) in bar

Accuracy Class

AC

Lock-up pressure Class

SG

0.3 to 0.5

> 0.5 to 1

> 1 to 2.5

> 2.5 to 5

> 5

10

10

2.5

1

1

30

20

10

10

5