Pilot-operated Active Gas Pressure Regulator According to DIN EN 334 (operating with auxiliary energy from the inlet pressure range)
| Application | Device used for gas distribution |
|---|---|
| Compact design | |
| Active and monitor regulator in one housing | |
| Active with fail-open function | |
| Monitor with fail-close function | |
| Less parts, easy to maintain | |
| Quiet operation | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE-registration according to PED | |
| Max. admissible pressure PS | =100 bar |
| Max. inlet pressure pu max | up to 100 bar |
| Outlet pressure range Wd | 0.3 bar to 90 bar |
| Minimum pressure drop | 2 bar, others on enquiry |
| Max. pressure drop | 90 bar |
| Class of lock-up pressure zone | SZ 2.5 |
| Active regulator applicable with pilot | - RMG 630 (two-stage design) - RMG 630-1 (single-stage design) for inlet pressure variation up to 15 bar |
| Monitor regulator applicable with pilot | - RMG 650 (single/double stage design) |
| Connection | - DIN flange PN 40 and - Flange Class 300, Class 600 according to ANSI 16.5 With pipe sizes inlet/outlet - DN 50/100, DN 80/150, DN 100/200 |
| All mechanical components of this device are without ignition sources. As such, they are not subject to ATEX 95 (94/9/EC). All electrical components used with this device fulfil the ATEX requirements. |
|