DeutschlandGroßbritannienPolenRusslandChina
Serving the Gas Industry Worldwide
RMGSitemapContact usImprint / Legal NoticeDruckenPDF

Gas pressure regulator RMG 505

Pilot-operated Active Gas Pressure Regulator According to DIN EN 334 (operating with auxiliary energy from the inlet pressure range)

Application Device used for gas distribution
  Compact design
  Active and monitor regulator in one housing
  Active with fail-open function
  Monitor with fail-close function
  Less parts, easy to maintain
  Quiet operation
  Suitable for non-aggressive gases, other gases on enquiry
   
  CE-registration according to PED
   
Max. admissible pressure PS =100 bar
Max. inlet pressure pu max up to 100 bar
Outlet pressure range Wd 0.3 bar to 90 bar
Minimum pressure drop 2 bar, others on enquiry
Max. pressure drop 90 bar
Class of lock-up pressure zone SZ 2.5
Active regulator applicable with pilot - RMG 630 (two-stage design)
- RMG 630-1 (single-stage design) for inlet pressure variation up to 15 bar
Monitor regulator applicable with pilot - RMG 650 (single/double stage design)
Connection - DIN flange PN 40 and
- Flange Class 300, Class 600
according to ANSI 16.5
With pipe sizes inlet/outlet
- DN 50/100, DN 80/150, DN 100/200
  All mechanical components of this device are without ignition sources. As such, they are not
subject to ATEX 95 (94/9/EC). All electrical components used with this device fulfil the ATEX
requirements.