Pilot-operated Gas Pressure Regulator According to DINEN 334 (operating with auxiliary energy from the inlet pressure range) with Incorporated SSV According to DINEN 334/14382
| Application | Device for transfer stations in gas transport networks for power plants and industrial facilities |
|---|---|
| Wide inlet pressure range | |
| Outlet DN double as inlet DN | |
| Less parts, easy to maintain, quiet operation | |
| Grid plate for noise reduction | |
| Also available with metal foam for additional noise reduction | |
| Version with Safety Shut-off Valve (SSV), actuators K 1a, K 2a/1, K 2a/2, K 10a, K 11a/1, K 11a/2, K 16, K 17, K 18, K 19 | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE-registration according to PED | |
| Max. admissible pressure PS | = 100 bar |
| Max. inlet pressure pu max | up to 100 bar |
| Outlet pressure range Wd | 0.3 bar to 90 bar |
| Minimum pressure drop | 1.5 bar (4 bar for DN 25/25), others on enquiry |
| Max. pressure drop | 90 bar |
| Class of lock-up pressure zone |
SZ 2.5 |
| SSV setting range for overpressure | Wdo 50 mbar to 90 bar |
| For underpressure | Wdu 10 mbar up to 90 bar |
| Connection |
- DIN flange PN 40 and Class 150 according to ANSI 16.5 for DN 25/25 - Flange Class 300, Class 600 according to ANSI 16.5 With pipe sizes inlet/outlet - DN 25/25, DN 25/50, DN 50/100, DN 80/150, DN 100/200, DN 150/300 |