Gas pressure regulator RMG 502

Pilot-operated Gas Pressure Regulator According to DINEN 334 (operating with auxiliary energy from the inlet pressure range)

Application Device for transfer stations in gas transport networks for power plants and industrial facilities
  Wide inlet pressure range
  Pilot Series RMG 630
  RMG 630-1 (formerly RMG 640), singlestage type for inlet pressure varation < 15 bar
  Outlet DN double as inlet DN
  Less parts, easy to maintain, quiet operation
  Grid plate for noise reduction
  Also available with metal foam for additional noise reduction
  Suitable for non-aggressive gases, other gases on enquiry
   
  CE-registration according to PED
   
Max. admissible pressure PS =100 bar
Max. inlet pressure pu max up to 100 bar
Outlet pressure range Wd 0.3 bar to 90 bar
Min pressure drop approx. 1.5 bar, others on enquiry
Max. pressure drop 90 bar
Class of lock-up pressure zone SZ 2.5
Connection - Flange PN 40 and
- Flange Class 300,
Class 600 according to ANSI 16.5
With pipe sizes inlet/outlet
- DN 25/50, DN 50/100, DN 80/150,
DN 100/200, DN 150/300, DN 200/300
   
   
All mechanical components of this device are without potential ignition sources
and / or hot faces. They are not subject to ATEX 95 (94/9/EC).
All electronic accessories, on the other hand, meet ATEX requirements.