Pilot-operated Gas Pressure Regulator According to DIN EN 334 (operating with auxiliary energy from the inlet pressure range)
| Application | Device for transfer stations in gas transport networks for power plants and industrial facilities |
|---|---|
| Wide inlet pressure range | |
| Pilot Series RMG 630 | |
| RMG 630-1 (formerly RMG 640), singlestage type for inlet pressure varation < 15 bar | |
| Outlet DN double as inlet DN | |
| Less parts, easy to maintain, quiet operation | |
| Grid plate for noise reduction | |
| Also available with metal foam for additional noise reduction | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE-registration according to PED | |
| Max. admissible pressure PS | =100 bar |
| Max. inlet pressure pu max | up to 100 bar |
| Outlet pressure range Wd | 0.3 bar to 90 bar |
| Min pressure drop approx. | 1.5 bar, others on enquiry |
| Max. pressure drop | 90 bar |
| Class of lock-up pressure zone | SZ 2.5 |
| Connection |
- Flange PN 40 and - Flange Class 300, Class 600 according to ANSI 16.5 With pipe sizes inlet/outlet - DN 25/50, DN 50/100, DN 80/150, DN 100/200, DN 150/300, DN 200/300 |
| All mechanical components of this device are without ignition sources. As such, they are not subject to ATEX 95 (94/9/EC). All electrical components used with this device fulfil the ATEX requirements. |