Pipe sizes |
Valve seat diameter in mm |
Flow rate coefficient KG* in m³/(h · bar) |
Face-to-face in mm |
|---|---|---|---|
|
DN 50/100 |
30 37 52 |
450 650 1150 |
450 |
|
DN 80/150 |
37 52 81 |
750 1400 2400 |
500 |
|
DN 100/200 |
52 81 102 |
1700 3400 3800 |
650 |
|
Load limiting stage |
Control stage |
|||||
|---|---|---|---|---|---|---|
|
Measuring unit |
Wire Ø |
Specific outlet pressure range Wds in bar |
Measuring unit |
Wire Ø |
Colour coding |
Specific outlet pressure range Wds in bar |
|
M |
3.3 (green) |
0.1 to 1.5 |
N |
2,5 3 3.5 4 5 |
white yellow green red blue |
0.01 to 0.04 0.02 to 0.06 0.04 to 0.12 0.08 to 0.2 0.1 to 0.5 |
|
5 (silver) |
0.5 to 5 |
M |
3.3 4 4.7 |
green blue brown |
0.3 to 1.5 1 to 2.5 2 to 3.5 |
|
|
Setpoint spring |
Outlet pressure range Wds |
|||
|---|---|---|---|---|
|
Spring |
Wire Ø |
Colour coding |
||
|
Control stage |
2 3 4 |
4.5 5 6.3 |
black grey brown |
1 to 5 bar 2 to 10 bar 5 to 15 bar |
|
Automatic load-limiting stage |
5 |
green |
0.5 to 15 automatic: above pd |
|
|
Outlet pressure range (pdrange ) |
Accuracy Class AC |
Lock-up pressure Class SG |
|---|---|---|
|
10 to 20 mbar > 20 to 30 mbar > 30 to 50 mbar > 50 to 100 mbar > 100 to 500 mbar > 0.5 to 2.5 bar > 2.5 to 5 bar > 5 bar |
20 10 10 5*/10 5 2.5 1 1 |
50 30 20 10*/20 10 10 10 5 |
|
Actuator system |
Overpressure Wdo in bar |
Underpressure Wdu |
|---|---|---|
|
K 4 K 5 K 6 K 10a K 16 K 17 |
0.04 to 0.5 0.2 to 1.5 0.6 to 4.5 0.05 to 1.5 0.8 to 16 |
5 to 60 mbar 15 to 120 mbar 40 to 300 mbar 10 to 120 mbar
|