Pilot-operated Gas Pressure Regulator According to DINEN 334 (operating with auxiliary energy from the inlet pressure range) with Incorporated SSV According to DINEN 334/14382
| Application | Device for offtake stations in gas transmission as well as power plants and industrial facilities |
|---|---|
| Large inlet pressure range | |
| With inline Pilot RMG 620 or Pilot Series RMG 630 (externally) | |
| RMG 630-1 (formerly RMG 640), singlestage type for inlet pressure variation <15 bar | |
| Also available with Safety Shut-off Valve (SSV) DN 25 (PN 16): actuator system K 1a, K 2a DN 50 thru DN 100 (inlet pipe sizes): - K 4, K 5, K 6 (thru PN 25) - K 10a, K 16, K 17 (thru Class 300) SSV setting range Wdo 40 mbar to 40 bar Wdu 5 mbar to 40 bar |
|
| Less parts, easy to maintain, quiet operation | |
| Noise reduction can be retrofitted | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE registration according to PED |
|
| Max. admissible pressure PS | = 50 bar |
| Max. inlet pressure pu max | up to 50 bar |
| Outlet pressure range | Wd 20 mbar to 40 bar |
| Minimum pressure drop 0.5 bar, others on enquiry |
|
| Class of lock-up pressure zone | SZ 2.5 |
| Flange connection (optional): | - Output DN = Input DN |
| DN 25 | DIN flange PN 16, PN 25, Class 150 according to ANSI 16.5 - Output DN = 2 x Input DN |
| DN 50 thru DN 100 | DIN flange PN 16, PN 25, PN 40 and Flange Class 150 and Class 300 according to ANSI 16.5 |