Valve specifications

Pipe sizes

Valve seat diameter

in mm

Flow rate coefficient

KG*in m3 /(h · bar)

Max. inlet pressure

Δ pu max in bar

Face-to- face dimension

in mm

without noise reduction

with noise reduction

DN 25

25

31

370

460

360

440

20

184

DN 50

50

31

1500

900

1300

800

20

254

DN 80

80

60

3000

2500

2700

2300

20

298

DN 100

100

80

60

4500

4000

3200

3600

3300

2900

20

352

DN 150

140

100

11900

6100

10400

5300

20

451

*) Flow rate coefficient for natural gas: (ρb = 0.83 kg/m³, t =15 °C)

Specific outlet pressure range with pilot BD-RMG 600

Control stage

Setpoint spring

Specific outlet
pressure range

Wds in bar

Measuring unit

Spring
no.

Wire Ø
in mm

Colour coding

LP

1047

TX002

TX003


3.7

4.5

blue


light blue

15 mbar to 140 mbar

25 mbar to 200 mbar

150 mbar to 500 mbar

MP

1047

TX002

TX003


3.7

4.5

blue


light blue

140 mbar to 350 mbar

350 mbar to 2 bar

2 bar to 4 bar

HP

TX002

TX003

3.7

4.5


light blue

700 mbar to 4 bar

4 bar to 8 bar

Specific outlet pressure range with pilot RMG 610 (RS 10d)

Load-limiting stage

Control stage

Measuring unit

Wire Ø
in mm

Specific outlet pressure range

Wds in bar

Measuring unit

Wire Ø
in mm

Colour coding

Outlet
pressure range

Wds

M

3.3

(green)

0.1 to 1.5

N

2.5


3


3.5


4


5

white


yellow


green


red


blue

10 mbar to 40 mbar

20 mbar to 60 mbar

40 mbar to 120 mbar

80 mbar to 200 mbar

100 mbar to 500 mbar

4.7

(silver)

0.5 to 5

M

3.3


4

4.7

green


blue

brown

300 mbar to 1.5 bar

1 to 2.5 bar

2 to 3.5 bar

Specific outlet pressure range with pilot RMG 650

Setpoint spring

Specific outlet
pressure range

Wds in bar

Spring
no.

Wire Ø
in mm

Colour coding

Control stage

2

3

4

4.5

5

6.3

black

grey

brown

1 to 5

2 to 10

5 to 15

Automatic load-limiting stage

5

green

to 15

automatic 0.5 above pd

Accuracy Class and lock -up pressure Class

Outlet pressure range

(pd range)

Accuracy Class

AC

Lock-up pressure Class

SG

10

5

5

2.5

1

1

50

20

10

10

10

5

Setting range of SSV control element

Actuator system

Overpressure

Wdo

Underpressure

Wdu

50 mbar to 2.3 bar

400 mbar to 7 bar

2 to 20 bar

10 mbar to 300 mbar

60 mbar to 1 bar


2 bar to 15 bar