Pilot-operated Gas Pressure Regulator According to DIN EN 334 ( operating with auxiliary energy from the inlet pressure range) with Incorporated Direct-acting SSV According to DIN EN 334 / 14382
| Application | Device for offtake stations in gas transmission as well as commercial and industrial facilities |
|---|---|
| Excellent for dynamic regulating lines (i.e., gas furnaces) | |
| Diaphragm assembly with inlet pressure compensation optionally with Safety Relief Valve (SRV) or safety diaphragm | |
| Optionally available with Safety Shut-off Valve (SSV) with in-line flow | |
| Noise reduction optional | |
| Very easy to maintain due to exchangeable functional units (cartridge assembly) | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE-registration according to PED |
|
| Max. admissible pressure PS | = 20 bar |
| Max. inlet pressure pu max | up to 20 bar |
| Outlet pressure range: | Wd 20 mbar up to 4 bar |
| Class of lock-up pressure zone | SZ 2.5 |
| SSV setting range | Wdo 25 mbar up to 5.2 bar Wdu 5 mbar up to 400 mbar |
| SRV setting range | Wd 15 up to 90 mbar above pds |
| Connection | DIN flange PN 16 or Class 150 according to ANSI 16.5, DN 25 thru DN 150 Other flange types on enquiry |