Gas pressure regulator RMG 361

Valve data

pipe size valve seat dia.
in mm
valve flowrate coefficient
KG* in m3/h
face-to-face
dimensions in mm
with noise reduction without noise reduction
25 25 360 370 184
31 440 460
50 31 700 800 254
50 1100 1400
80 60 2000 2200 298
80 2400 2700
100 60 2600 2900 352
80 3000 3700
100 3300 4200
*) for natural gas (ρn = 0,83 kg/m3)

Specific outlet pressure ranges

setpoint spring outlet pressure range Wds
in bar
no. colour
O DA1* black / DA2* blue 0.020 to 0.030
1 grey 0.025 to 0.050
2 yellow 0.045 to 0.100
3 brown 0.090 to 0.200
4 bright red 0.150 to 0.300
5 dark red 0.250 to 0.400
6 light blue 0.350 to 0.500
*) DA = diaphragm assembly (DA1 = size 1)

Accuracy class, lock-up pressure class, lock-up pressure zone

accuracy class AC ≥5
lock-up pressure class SG ≥10
lock-up pressure zone SZ 2.5