Spring-loaded gas pressure regulator, direct acting
| Application | for industrial and domestic users |
|---|---|
| suitable for dynamic regulating lines (gas furnaces) | |
| suitable for natural gas and non-corrosive gases | |
| can be provided with various valve seats of different sizes | |
| valve with inlet pressure compensation | |
| diaphragm assembly provided with: safety relief valve SBV for gas leakages (pa max 0.5 bar) safety diaphragm (DN 25, DN 50) |
|
| type with safety cut-off valve (SAV) with axial passage (actuator type K1a) | |
| alternative with noise reduction | |
| CE-registration according to PED DIN-DVGW approval |
|
| Max. inlet pressure pu max | 10 bar |
| Outlet pressure range Wd | 0.020 bar to 0.5 bar |
| KG-value (in m³/h) | with noise reduction 360 to 3300 without noise reduction 370 to 4200 |
| SAV-adjustment ranges |
Wdo 0.050 bar to 1.5 bar Wdu 0.010 to 0.12 bar |
| SBV-adjustment range |
Wd 0.015 to 0.140 bar above pas |
| connections |
flanged to DIN PN 16 DN 25 to DN 100 |