Pilot-operated Gas Pressure Regulator According to DINEN 334 (operating with auxiliary energy from the inlet pressure range) with Incorporated Direct-acting SSV According to DINEN 334/14382
| Application | Device for offtake stations in gas transmission as well as commercial and industrial facilities |
|---|---|
| Large inlet pressure range | |
| Various valve seat diameters for best adaptation to operating conditions | |
| High regulating accuracy | |
| Diaphragm assembly with inlet pressure compensation |
|
| Optionally with pilot, models RMG 610 (RS 10d) or RMG 650 | |
| Also available with Safety Shut-off Valve (SSV) DN 25, DN 50: Actuator systems K 1a, K 2a DN 80, DN 100: Actuator systems K 4, K 5, K 6 |
|
| Very easy to maintain thanks to exchangeable functional units (cartridge assembly) | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE registration according to PED |
|
| Max. admissible pressure PS | = 16 bar |
| Max. inlet pressure pu max | up to 16 bar |
| Outlet pressure range Wd | 10 mbar up to15 bar |
| Minimum pressure drop | 0.2 bar, others on enquiry |
| Class of lock-up pressure zone | SZ 2.5 |
| SSV setting range | Wdo 50 mbar up to 4.5 bar Wdu 5 mbar up to 300 mbar |
| Connection | DIN flange PN 16 DN 25, 50, 80 and 100 Other flanges on enquiry |