DeutschlandGroßbritannienPolenRusslandChina
Serving the Gas Industry Worldwide
RMGSitemapContact usImprint / Legal NoticeDrucken  

Gas pressure regulator RMG 330

Valve specifications

Pipe sizes

Valve seat diameter

in mm

Flow rate coefficient

KG*

in m³/(h · bar)

Inlet pressure range

Δ pu in bar

(in brackets: max. inlet pressure, see page 81)

Face-to-face dimension

in mm

Diaphragm assembly

Size 1

Diaphragm assembly

Size 2

DN 25

20

33

200

420

16

10 (16)

200

DN 50

20

33

200

500

16

10 (16)

230

DN 80

25

31

41

50

400

850

1,400

1,750

16

10 (16)

8 (16)

5 (10)

16

16

16

10 (16)


420

DN 100

25

31

41

50

60

80

100

400

850

1,400

1,750

3,000

4,200

4,700

16

16

16

10 (16)

10 (16)

6 (12)

4 (8)



500

*) Flow rate coefficient for natural gas: (ρb = 0.83 kg/m³, t =15 °C)

Specific outlet pressure ranges for diaphragm assembly 1

Setpoint spring

Specific outlet pressure range

Wds in mbar

Spring
no.

Wire Ø
in mm

Colour
coding

Measuring
unit 1*

0

1

2

3

4

5

6

7

8

9

3.6

4

4.5

5.3

6.3

7

7.5

8.5

9.5

10.5

signal blue

grey

yellow

brown

light red

dark red

light blue

white

green

black

20 to 30

25 to 50

45 to 100

90 to 200

150 to 300

250 to 400

350 to 500

450 to 600

550 to 800

650 to 1,000

*) Version with incorporated Safety Relief Valve (SRV) or with additional safety diaphragm for outlet pressure ranges only up to pd max 0.5 bar

Specific outlet pressure ranges for diaphragm assembly 2

Setpoint spring

Specific outlet pressure range

Wds in mbar

Spring
no.

Wire Ø
in mm

Colour
coding

Measuring
unit 2

5

6.3

7

8

9

10

11

12

13

14

blue

grey

yellow

brown

light red

dark red

light blue

white

green

black

20 to 30

25 to 50

45 to100

90 to 200

150 to 300

250 to 400

350 to 500

450 to 600

550 to 800

650 to 1,000

Accuracy class and lock-up pressure class

Outlet pressure range

(pd range in mbar)

Accuracy Class

AC

Lock-up pressure Class

SG

20 to 30

> 30 to 100

> 100 to 500

> 500 to 1,000

10*/20

5*/10

5

2.5

30*/50

10*/20

10

10

*) Values apply to inlet pressure variation up to 6 bar max.

Setting range of SSV control element

Actuator system

Overpressure

Wdo in bar

Underpressure

Wdu

K 1a

K 2a

K 4

K 5

K 6

0.05 to 1.5

0.4 to 5.2

0.04 to 0.5

0.2 to 1.5

0.6 to 4.5

10 to 120 mbar

60 to 400 mbar

5 to 60 mbar

15 to 120 mbar

40 to 300 mbar