Direct-acting Gas Pressure Regulator with Incorporated Direct-acting SSV According to DINEN 334/14382
| Application | Device for offtake stations in gas transmission as well as commercial and industrial facilities |
|---|---|
| Suitable for dynamic regulating lines (gas furnaces) | |
| Large inlet pressure range | |
| Best adaptation to operating conditions thanks to various valve seat diameters | |
| Diaphragm assembly with inlet pressure compensation | |
| Regulating assembly optionally with: - Safety relief valve - Safety diaphragm |
|
| Also available with safety shut-off valve (SSV) DN 25, DN 50: Actuator systems K 1a, K 2a DN 80, DN 100: Actuator systems K 4, K 5, K 6 |
|
| Easy to maintain thanks to exchangeable functional units (cartridge assembly) | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE registration according to PED |
|
| Max. admissible pressure PS | = 16 bar |
| Max. inlet pressure pu max | up to 16 bar |
| Outlet pressure range Wd | 20 mbar up to1 bar |
| Class of lock-up pressure zone | SZ 2.5 |
| SRV setting range Wd | 10 mbar to 300 mbar above pds (only up to pd max = 0.5 bar) |
| SSV setting range | Wdo 50 mbar up to 1.5 bar Wdu 10 mbar to 120 mbar |
| Connection | DIN flange PN 16 or Class 150 according to ANSI 16.5 |