Valve seat Ø in mm |
Flow rate coefficient KG* in m³/(h · bar) |
Face-to-face dimension in mm |
|---|---|---|
|
11 |
65 |
160 |
|
Setpoint spring |
Specific outlet pressure range Wds |
|||
|---|---|---|---|---|
|
No. |
Wire Ø in mm |
Colour coding |
Measuring |
Measuring |
|
1 2 3 4 5 6 7 |
2.5 3 3.6 4 4 4.5 5.3 |
grey yellow ivory light red green light blue dark blue |
20 to 45 mbar 35 to 100 mbar 80 to 200 mbar 150 to 300 mbar 250 to 400 mbar 300 to 500 mbar 450 to 800 mbar |
0.6 to 0.8 bar 0.6 to 2 bar |
|
Outlet pressure range (pd range) |
Accuracy Class AC |
Lock-up pressure Class SG |
|---|---|---|
|
20 to 30 mbar > 30 to 50 mbar > 50 to 500 mbar > 0.5 to 2 bar |
10 10 5 2.5 |
30 20 10 10 |
|
Actuator system |
Overpressure Wdo |
Underpressure Wdu |
|---|---|---|
|
K 1a K 2a |
50 mbar to 1.5 bar 400 mbar to 5.2 bar |
10 to 120 mbar 60 to 400 mbar |