Direct-acting Gas Pressure Regulator with Incorporated Direct-acting SSV According to DINEN 334/14382/33822
| Application | Device for offtake stations in gas transmission as well as commercial and industrial facilities |
|---|---|
| Suitable for non-aggressive gases, other gases on enquiry | |
| Diaphragm assembly with inlet pressure compensation | |
| Excellent for dynamic regulating lines (e.g., gas furnaces) | |
| Optional HTB design (pu max = 5 bar) | |
| Large inlet pressure range | |
| Optional internal/external measuring impulse connection | |
| Optionally with vent valve RMG 915 with regulating assembly (SRV blocked) or safety diaphragm | |
| Excellent regulating dynamics | |
| Regulating assembly optionally: - in standard design - with safety relief valve (SRV) (only up to pd max 0.5 bar) |
|
| With or without safety shut-off valve (SSV) | |
| SSV design optionally with control element K 1a or K 2a |
|
| Very easy to maintain thanks to exchangeable functional units (cartridge assembly) | |
| CE registration according to PED |
|
| Max. admissible pressure PS | = 16 bar |
| Max. inlet pressure pu max | up to 16 bar |
| Outlet pressure range Wd | 20 mbar up to 2 bar |
| Class of lock-up pressure zone | SZ 2.5 |
| SSV setting range | Wdo 50 mbar up to 4.5 bar Wdu 10 mbar up to 0.4 bar |
| SRV setting range (measuring unit 1 only) | Wd 10 mbar to 160 mbar above pds |
| Connection | DIN flange PN 16 or Class 150 according to ANSI 16.5 |