Pilot-operated Gas Pressure Regulator According to DINEN 334 ( operating with auxiliary energy from the inlet pressure range) with Incorporated Direct-acting SSV According to DINEN 334 / 14382
| Application | Device for offtake stations in gas transmission as well as commercial and industrial facilities |
|---|---|
| Large inlet pressure range | |
| Noise reduction optional | |
| High regulating accuracy | |
| Diaphragm assembly with inlet pressure compensation | |
| Optionally with pilot, models RMG 610 (RS 10d), RMG 650 and BD-RMG 600 | |
| Optionally available with Safety Shut-off Valve (SSV) with in-line flow | |
| Very easy to maintain thanks to exchangeable functional units (cartridge assembly) | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| CE registration according to PED |
|
| Max. admissible pressure PS | = 20 bar |
| Max. inlet pressure pu max | up to 20 bar |
| Outlet pressure range: | Wd 10 mbar to 15 bar |
| Class of lock-up pressure zone | SZ 2.5 |
| Minimum pressure drop | 0.2 bar, others on enquiry |
| SSV setting range | Wdo 50 mbar to 20 bar Wdu 10 mbar to 15 bar |
| Connection | DIN flange PN 16 and Class 150 according to ANSI 16.5, DN 25 thru DN 150 Other flange types on enquiry |