Spring-loaded gas pressure regulator, direct acting
| Application | for industrial and laboratory applications |
|---|---|
| for auxiliary setting-ups within gas pressure regulating devices according to G 491 | |
| suitable for natural gas and non-corrosive gaseous media | |
| 3-stage special version with throttle and safety relief valve (SBV) stage as additional protective device for the outlet pressure stage | |
| large outlet pressure range | |
| high regulating precision: inlet pressure variations lead only to very small outlet pressure deviations |
|
| easy operation and maintenance | |
| Max. inlet pressure pu max | 100 bar |
| Outlet pressure range Wd | 0,02 bar to 1 bar |
| SBV adjustment range Wd | 0.05 bar to 1.2 bar |
| Connections | screw connection without brazing to DIN 2353 for external pipe dia. 10 mm |
| Comment |
A throttle limits the maximal flow to qn= 2 m³/h according to the application range, so that the maximal volume of the SBV-stage equalizes the volume for pu max. I.e. the diameter of the throttle and the SBV-orifice are fixed so that more gas is always re-lieved to the atmosphere through the safety relief valve stage than can penetrate into the device, even during failure conditions. Therefore, an uncontrolled increase of the outlet pressure is avoided in case of defects. |