Valve data

Valve seat diameter
in mm

5

6

8

12

18

23

Flow rate coefficient
KG in m³ /(h · bar) for natural gas
Pb = 0.83 kg/m³ , t = 15 °C)

12

25

50

125

200

250

Max. inlet pressure variation

Δ pu max in bar

(Please consider pressure rating)

100

100

100

80

40

25

Face-to-face dimensions: 234 to 440 mm depending on connection

Specific outlet pressure range with pilot RMG 610, preferably with actuator 2

Load limiting stage

Pilot stage

Measuring unit

Wire Ø
in mm

Specific outlet
pressure range

Wds in bar

Measuring unit

Wire Ø
in mm

Colour coding

Specific outlet
pressure range

Wds in bar

M

3.3

(green)

0.1 to 1.5

N

2,5

3

3,5

4

5

white

yellow

green

red

blue

0.01 to 0.04

0.02 to 0.06

0.04 to 0.12

0.08 to 0.2

0.1 to 0.5

5

(silver)

0.5 to 5

M

3,3

4

4,7

green

blue

brown

0.3 to 1.5

1 to 2.5

2 to 3.5

Specific outlet pressure range with pilot RMG 650, preferably with actuator 1

Setpoint spring

Specific outlet
pressure range

Wds in bar

Spring
no.

Wire Ø
in mm.

Colour coding

Pilot stage with diaphragm measuring unit

0

1

2

3

4

5

4.5

3.6

4.5

5

6.3

7

black

blue

black

grey

brown

red

0.3 to 1**

0.5 to 2

1 to 5

2 to 10

5 to 20

10 to 40

Pilot stage metal-harmonica measuring unit

6

7

8/7

9

green

white

10 to 50

20 to 90

Control stage

5

green

0.5 to 15

automatic: above pd

Accuracy Class and lock -up pressure Class

Outlet pressure range (pdrange ) in bar

Accuracy Class AC

with valve seat diameters up to 8 mm

Accuracy Class AC

with valve seat diameters up to 12 mm

Lock-up pressure Class

SG

0.01 to 0.03

>0.03 to 0.1

>0.1 to 0.5

>0.5 to 1

>1 to 2.5

>2.5 to 5

>5

5

5

5

2.5

2.5

1

1

10

5*/10

5

2.5*/5

2.5

1

1

30

20

10

10

10

10

5

*) This better accuracy Class applies if inlet pressure variations are smaller than half the max. inlet pressure pu max.