Pilot-operated Gas Pressure Regulator
| Application | Device for offtake stations in gas transmission and distribution, as well as power plants and industrial facilities |
|---|---|
| Wide range of operating conditions, including high pressure | |
| High regulating accuracy | |
| Diaphragm valve/grid plate design | |
| Few parts, easy to maintain, quiet operation | |
| Pilot options including RMG 620 (integrated in top cover), RMG 630 and RMG 640a | |
| Can be fitted with an over-pressure cut-off valve (OPCO) or a combined under-/overpressure cut-off valve (UPCO/OPCO) | |
| Suitable for natural, non-aggressive and manufactured gases; nitrogen, carbon dioxide and propane; and other gases upon enquiry | |
| CE registration according to PED | |
| Max. inlet pressure pu max | up to 25 bar |
| Outlet pressure range Wd | 0.02 bar to 25 bar |
| Minimum pressure drop | 0.5 bar |
| Class of lock-up pressure zone | SZ 2.5 |
| SSV setting range | Wdo 0.055 bar to 14 bar Wdu 0.03 bar to 3.5 bar |
| Temperature range | –20 to +60 °C |
| Connection (optional) | Output DN = Input DN DN 25 to DN 100: DIN flange PN 16, PN 25 and flange according to Class (ANSI) 150 RF |
| Output DN = 2 x Input DN DN 50/100, DN 80/150 and DN 100/200, DIN flange PN 16, PN 25 and PN 40, flange according to Class (ANSI) 150 and Class (ANSI) 300 RF |
|