Meter for volume at base conditions TEC 24

Compact gas volume meter

Application electronic volumeter with integrated volume corrector (battery-operated, service life min. 6 years)
  special version for corrosive gas
  electronic, battery-operated counting mechanism
(service life min. 6 years)
  torqueless metering system showing total gas flow in volume units (working cubic meter)
  high accuracy
  horizontal or vertical gas flow
  standard LF and HF frequency outputs
  calculation of the K coefficient acc. to GERG 88S or AGA 8 gross method 1
  serial RS 485 interface with Modbus protocol
  current output (external power supply unit required)
  explosion protection: II 2 G EEx ib[ia] II C T4/T3
  read-out and parameterization program EC Visit
Max. service pressure pmax 100 bar
Meter sizes G 40 to G 16000
(Qmax 100 m³/h to Qmax 25000 m³/h)
Connections standard
DN 50 to DN 600
flanged to PN 100 and ANSI 600

optional
DN 50 to DN 250 in sandwich design
DN 25 and DN 40 threaded-end sandwich design