DeutschlandGroßbritannienPolenRusslandChina
Serving the Gas Industry Worldwide
RMGSitemapContact usImprint / Legal NoticeDruckenPDF  

Flame arrester RMG 931-A

Pipe Protection

Protection System Tube protection against deflagration
  Tube protection against detonation
  Protection against continuous fire
Approval EC-type examination certificate based on directive 94/9/EC, according to ATEX 95 and EN 12874
Protection Gas/air or steam/air mixtures of the following explosion groups:
– I (methane) NSW ≥ 1.14 mm
– IIA (D) NSW ≥ 0.90 mm
Pipe Sizes DN15, DN20, DN25, DN32
1/2", 3/4", 1", 11⁄4"
Connection Standards DIN 2501 PN10
ANSI B16.5 – 150 RF
Materials Strip protection:
Stainless steel
Body/cap:
Carbon steel, stainless steel
Coating Optional

RMG 931-A

Flame arrester RMG 931-A