On/Off Valve
| Application | Diaphragm break safety device for actuator systems K 1a, K 2a, K 2a/1, K 2a/2, K 4, K 5, K 6, K 10a, K 11a/1, K 11a/2 |
|---|---|
| Component of a Safety Shut-off Valve equipped with a diaphragm break safety device | |
| Installed on the vent line of SSV actuator | |
| Suitable for non-aggressive gases, other gases on enquiry | |
| SEP design according to PED | |
| Max. admissible pressure PS | = 100 bar |
| Max. operating pressure pmax | up to 100 bar |
| Tripping pressure for closing | 20 mbar approx. |
| Connection | Inlet: - External thread M 16 x 1.5 or G 1/2" |
| Outlet: Connection: Pipe connections according to DIN EN ISO 8434-1 (DIN 2353), PN 100, for pipe diameters 10 mm |