Filter RMG 906,RMG 906a and RMG 906 a't'

Gas Filter – Cellular Filter According to DIN 3386

Application Filter for distribution stations as well as power plants and industrial facilities
  Compact design
  High filtration efficiency
  Low pressure loss Δp
  Exchangeable filter insert
  Easy cleaning and environmentally friendly disposal of filter mesh
  Suitable for non-aggressive gases, other gases on enquiry
   
  CE registration according to PED
   
  All mechanical components of this device are without ignition sources. As such, they are not subject to ATEX 95 (94/9/EC). All electrical components used with this device fulfil the ATEX requirements.
   
   
RMG 906  
Max. admissible pressure PS = 16 bar
Max. operating pressure pmax up to 16 bar
Max. flow velocity for sizing up to 20 m/s
Max. pressure drop Δp 50 mbar (for clean filter)
Limit for soiled filter inser Δpmax 500 mbar
Filter material pleated special paper, three grades: 10 μm, 4 μm and 2 μm
Connection - DIN flange PN 16 (cast aluminium body) in DN 25, DN 50, DN 80 & DN 100
- DIN flange PN 16 (ductile iron body) in DN 150
   
   
RMG 906a, 906a a”t”  
Same features as RMG 906– plus: -2-stage dust separation
-Optional: magnet insert for collection of magnetic parts
-HTB design (RMG 906a”t”)
Max. admissible pressure PS = 25 bar
Max. operating pressure pmax up to 25 bar
Filter material pleated special paper, three grades: 10 μm, 4 μm and 2 μm
Connection - DIN flanges PN 16, PN 25
- Flange Class 150 according to ANSI 16.5 (ductile iron body) in DN 25, DN 50, DN 80, DN 100